Transformer Turns Ratio

Magnetic Balance

Transformer Turns Ratio

Magnetic Balance
File Size
381.1kb

Transformer turns ratio is measured by applying line frequency AC voltage to one winding of a transformer and measuring the induced voltage on the corresponding winding. Magnetic balance excites the transformer the same way, but instead of measuring the induced voltage on the corre-sponding winding, the induced voltage on the same winding is measured.

The is capable of performing a magneticbalance test on any vector configuration in under 30 seconds.  But what are the benefits to this method oftesting?